This site has been split into two specialist sites: monitoring and automation equipment at wel-electronics.com, medical products at wel-medical.com. This site remains as an archive.

30kVA.240VDC.220/380VAC SYNCHR/ATS/STS/BYPASS

30kVA.240VDC.220/380VAC/SYNCHR/ATS/STS/BYPASS inverter

30kVA.240VDC.220/380VAC/SYNCHR/ATS/STS/BYPASS inverter30kVA 240VDC 220/380VAC SYNCHR ATS STS BYPASS inverter

Purpose:

  • The inverter converts DC voltage into three-phase sinusoidal AC at 50 Hz.
  • The inverter can supply a wide range of industrial and domestic loads rated 220/380 V AC at 50 Hz, up to 30 kVA for three-phase loads and up to 10 kVA per phase for single-phase loads.
  • The inverter has a built-in automatic transfer switch (ATS) that transfers the load automatically between the mains incomer and the inverter according to the priority the user sets on the inverter's built-in controller.
  • The inverter has a built-in high-speed thyristor switch (static transfer switch) that transfers the load quickly between the mains incomer and the inverter.
  • The inverter monitors the state of the battery and the mains and indicates input and output status.

Distinctive features:

  • Pure sine wave output
  • Silent, high-efficiency operation
  • Apparent output power 30 kVA
  • A high-efficiency combined liquid and air cooling system with four cooling levels and five automatic operating modes.
  • The battery charge monitoring system extends battery life by reducing the number of charge-discharge cycles
  • A control panel with a blue-backlit LCD showing the inverter's output currents and voltages.
  • Six LED indicators show the inverter's status.
  • Audible warning signals indicating the various operating modes, faults and system problems.
  • Operating modes, the monitored battery and grid parameters, and the built-in ATS modes can all be programmed from the control panel.
  • Inverter run/fail signalling relay. Low standby consumption (under 20 W)
  • Automatic overload and over-temperature protection
  • Programmable deep-discharge battery protection
  • Soft start with heavy loads
  • Built-in high-speed thyristor ATS.
  • Built-in automatic bypass that transfers the load to mains supply if the battery is fully discharged or absent.

Operating manual for the 30kVA.240VDC.220/380VAC/SYNCHR/ATS/STS/BYPASS inverter