Phase-failure relays
ЕЛ-11М and ЕЛ-11М2 phase-failure relays
Phase-failure relays
Purpose:Phase-failure relays monitor the state of a three-phase network and protect the load against impermissible voltage deviations in one or more phases (phase imbalance or asymmetry), a change in phase sequence, and the loss of one or more phases.ЕЛ-11М
Distinctive features:- Microprocessor control with digital signal processing. No adjustment required.
- Monitoring of phase loss and phase sequence.
- Phase imbalance monitoring.
- Umin monitoring.
- Adjustable switch-off delay when the voltage falls below Umin.
- Hysteresis on re-closing.
- Output status shown on a bi-colour LED.
- Powered from the monitored network.
- Versions for nominal phase voltages of 220 V and 127 V.
- Galvanically isolated normally closed and normally open contacts.
Switching life at least 3×107. - DIN-rail mounting, 35 mm case.
Technical specifications:
- Power consumption, max: 4 W
- Mains frequency, (48 – 62) Hz
- Operating voltage, 380/220 V
- Maximum switched current for a resistive load — 8 A
- Maximum switched AC voltage — 250 V
- Overall dimensions, 86×35×60 mm
- Weight, max, 200 g.
- Operating temperature range (-25 – +55) °C
- Storage temperature, (-40 – +70) °C
- Timing accuracy: better than ±5%
- Climatic category УХЛ
- Mounting method and method of connecting external leads:
- for DIN-rail mounting;
- supply conductors connected via terminal blocks.
Datasheet for the ЕЛ11М phase-failure relay
ЕЛ-11М2
Distinctive features:- Microprocessor control with digital signal processing.
- No adjustment required.
- Phase loss monitoring.
- Phase sequence monitoring.
- Phase imbalance monitoring.
- Umin and Umax monitoring
- Neutral conductor break monitoring.
- Switch-off delay when the voltage falls below Umin or rises above Umax.
- Hysteresis (reset ratio) on re-closing.
- Input and output status shown on a bi-colour LED.
- Powered from the monitored network.
- Two groups of isolated changeover contacts
- DIN-rail mounting, narrow case (35 mm).
- Voltage setpoints, hysteresis and operating time can all be changed in software.
Technical specifications:
- Monitored circuit connection: three phases with neutral.
- Nominal operating voltage 380/220 V
- Mains frequency, 48 - 62 Hz
- Upper pickup threshold — 264 V
- Lower pickup threshold — 165 V
- Hysteresis, 10 V
- Pickup delay on Umin, and on loss of a phase — 1 s
- Pickup delay on Umax, and on complete loss of voltage on all three phases — 0.15 s
- Pickup delay on a change of phase sequence — 0.1 s
- Active power consumption, max: 3 W
- Insulation voltage input-to-contact and contact-to-contact — 1000 V
- Overall dimensions, 90×65×35 mm
- Weight, max, 200 g
- Operating temperature range (-25 – +55) °C
- Voltage pickup accuracy better than ±3%
- Delay timing accuracy: better than ±5%
- Climatic category УХЛ
- Protection rating IP20
- Mounting method and method of connecting external leads:
for DIN-rail mounting; supply conductors connected via terminal blocks - The terminals accept external conductors of at least 1.5 mm².
Datasheet for the ЕЛ11М2 phase-failure relay