БУАВР.ЭА.(1-3)Ф
БУАВР.ЭА.(1-3)Ф automatic transfer switch controller
for an ATS with two incomers and one load, one incomer being a generator set, with a selectable number of phases
Purpose:
- The БУАВР controls the automatic transfer from the main supply to the standby supply and back, on impermissible phase voltage deviations, phase imbalance or asymmetry, a change in phase sequence, or the loss of one or more phases in the "main" or "standby" network.
- The БУАВР can be used in distribution networks as part of:
- automatic transfer switching (ATS);
- emergency transfer switching. - The БУАВР monitors incomer status, controls magnetic contactors and motor-operated circuit breakers, indicates input and output status, and starts, stops and automatically restarts the generator set.
- The БУАВР.ЭА.Х.Х.(1-3)Ф works with single-phase and three-phase mains and generator sets.
- The БУАВР is built to climatic category У, placement category 2 per ДСТУ ГОСТ 15150-69, and is designed to operate at temperatures from -25°C to +55°C, relative humidity up to 80% and atmospheric pressure from 650 to 800 mm Hg.
- The БУАВР is intended for operation in a non-explosive atmosphere, free of gases and vapours in concentrations that attack metal and insulation, and free of saturated water vapour and conductive dust.
- Resistance to external mechanical factors — per ДСТУ ГОСТ 17516.1, group М6
- Permissible vibration: 1 to 35 Hz at an acceleration of no more than 4 m/s².
- The БУАВР is supplied from the monitored network whenever voltage is present on one of the phases (Table 1) of either incomer, or from a (12…24) V battery. When used in an ATS with motor-operated circuit breakers, an additional control power source is recommended.
- The БУАВР connects directly to 0.4 kV networks.
Operating manual for the БУАВР.ЭА.(1-3)Ф automatic transfer switch controller