БУАВР.C.58, 100, 127

БУАВР.С.58, C.100 and C.127 automatic transfer switch controllers

for transfer switching on 6-10 kV feeders with two incomers, two busbar sections and a bus-tie breaker

Purpose:

  • The БУАВР controls the automatic transfer from the main supply to the standby supply and back, on impermissible phase voltage deviations, phase imbalance or asymmetry, a change in phase sequence, or the loss of one or more phases on the first or second incomer.

  • The БУАВР can be used in distribution networks as part of:
    - automatic transfer switching (ATS);
    - emergency transfer switching.
  • The БУАВР monitors incomer status, controls the circuit breakers, and indicates input and output status.
  • The БУАВР is built to climatic category У, placement category 2 per ДСТУ ГОСТ 15150-69, and is designed to operate at temperatures from -25°C to +55°C, relative humidity up to 80% and atmospheric pressure from 650 to 800 mm Hg.
  • The БУАВР is intended for operation in a non-explosive atmosphere, free of gases and vapours in concentrations that attack metal and insulation, and free of saturated water vapour and conductive dust.
  • Resistance to external mechanical factors — per ДСТУ ГОСТ 17516.1, group М6
  • Permissible vibration: 1 to 35 Hz at an acceleration of no more than 4 m/s².
  • The БУАВР is supplied from the monitored network whenever voltage is present on one of the phases of either incomer, or from an additional control power source.
  • The БУАВР connects to 6 kV and 10 kV networks through an instrument transformer

Operating manual for the БУАВР.С.58, C.100 and C.127 automatic transfer switch controllers