БАП

Emergency supply unit, БАП, supply for vacuum circuit breakers, ВР0, ВР1, transformer substation, switchgear assemblies

Emergency unit
supply

Technical specifications:

  • The БАП is built as an electronic module housed in a plastic enclosure.
  • Overall dimensions are given in Figure 1.
  • Nominal input voltage when supplied from the mains (from the auxiliary services transformer) — 220 V
  • DC output voltage at nominal mains voltage with a vacuum circuit breaker connected — 290 V
  • Pickup voltage of the trip-enable relay, at the capacitor bank voltage — 187 V +2%.
  • БАП load capacitance, max 2000 µF
  • Nominal capacitance of the built-in capacitor that closes the breaker when supplied from the mains — 4700 µF
  • The time needed to prepare for tripping, while charging the capacitor bank built into a ВР1 vacuum circuit breaker, as a function of the current in the relay winding of the current transformer, is given in Table 1 (typical values).

  • Thermal withstand on the current inputs, for 1 min, A — 200
  • БАП weight, kg, max 2.5

Datasheet for the БАП

Data sheet for the БАП